DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 47
Bosch Security Systems | 8/04 | 4998153891C
Verified Alarm Timer
Address: 3412, 3413
Default: 1,14 (30 min.)
Selections:
0,0 (Disabled)
1,14 (30 min.) to 3,12 (60 min.)
This parameter sets the time for the Verified Alarm Timer. The amount of time entered in this parameter defines
the window of time in which two independent alarms must occur for the control panel to declare a verified alarm.
See the Glossary on page 148 for a definition of Verified Alarm.
Addresses 3412 and 3413 must be programmed when setting the Verified Alarm Timer. The system uses the
following formula to set the Verified Alarm Timer:
Address 3412 entry x 16 + Address 3413 entry = Verified Alarm Timer setting
For example, use the following steps to set the Verified Alarm Timer to 30 min.:
1. Enter “1” in Address 3412 (1 x 16 = 16).
2. Enter “14” in Address 3413 (16 + 14 = 30).
An entry of 0,0 disables the Verified Alarm Timer and Verified Alarm operation. Values from 1 to 29 operate as
30 min.. Values from 30 to 60 operate as entered (for example, with an entry of 31, the control panel declares a
verified alarm if two independent alarms occur within 31 min.). Values greater than 60 operate as 60 min..
See below for commonly used time settings:
1,14 = 30 min. (1 x 16 = 16 + 14 = 30 min.)
2,13 = 45 min. (2 x 16 = 32 + 13 = 45 min.)
3,12 = 60 min. (3 x 16 = 48 + 12 = 60 min.)