Bosch DS7200V2-EXP Guia do Utilizador Página 103

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 156
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 102
DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 103
Bosch Security Systems | 8/04 | 4998153891C
4.5.3 Global Zone Configuration
On-board Location EOL Resistor Value
Address: 1026
Default: 5 (Tamper-wired loops, single tamper-wired sensors)
Selections:
0 = No EOL Resistor
1 = 1 k EOL Resistor
2 = 2.2 k EOL Resistor
3 = 3.65 k EOL Resistor
4 = Zone Doubled, 2.2 k & 3.65 k EOL Resistors
5 = Tamper-wired loops, single tamper-wired sensors
6 = Tamper-wired loops, multiple tamper-wired sensors (up to 5 max)
This parameter applies to the control panel’s eight on-board sensor loops.
If zone doubling is turned on, the locations are paired as shown in Table 23.
Table 23: EOL Resistor Location Pairing for Zone
Doubling
Location (Sensor Loop)
EOL Resistor 1 2 3 4 5 6 7 8
3.65 k 1 2 3 4 5 6 7 8
2.2 k 9 10 11 12 13 14 15 16
Zone Response Options (for all zones)
Address: 1027
Default: 0
Selections: 0 to 3
Enter This Data Digit to Select Options
Zone Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Options Selected
Enable Smart Swinger
• •
Unverified Events Send Trouble Reports
Reserved
Reserved
Smart Swinger: If enabled, this option allows zones that were Swinger Shunted to report new alarm events if
they are faulted when Bell Time is running. The ARC receives alarm reports from zones that previously
reported as Swinger Shunted. When Bell Time is running, the Swinger Count applies to these zones. They
only send reports until Bell Time expires or until the swinger count is reached again at which time they
Swinger Shunt again. If these bypassed zones are faulted when Bell Time is not running, they remain Swinger
Shunted and do not send reports.
Unverified Events Send Trouble Reports: If this option is enabled, Fire Alarm with Verification zones that
have single, unverified events generate an Unverified Event report. Zones with the Cross Zone option enabled
that have a single pulse generate an Unverified Event report.
Vista de página 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 155 156

Comentários a estes Manuais

Sem comentários