DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 18
Bosch Security Systems | 8/04 | 4998153891C
Phone Line Fault Response Options
• Address: 0220
• Default: 0
• Selections: 0, 1, 3, 5, 7
Enter This Data Digit to Select Options
Phone Line Fault Response Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Phone Line Supervision
•
Enable Supervision (System Trouble at Keypad)
•
• • •
Burg Alarm & Strobe Functions, All On/Perimeter
Only
• •
Burg Alarm & Strobe Functions, Off
• •
Reserved
The control panel monitors the phone line for voltage only. If the voltage drops low enough (between 1 and 3 V)
for 40 sec, it declares a phone line fault. If the phone line voltage remains above 3 V for at least 40 sec, it declares
the phone line restored. See the ”Phone Line Fault Requires Reset” option in Phone Line Options on page 14.
When enabled, the Phone Line Fault event appears at all keypads for all areas. The control panel sends a Phone
Line Restore {100} report when a phone line fault event restores.
If the phone line fails (as described above), but restores before a Comm Fail event:
1. System detects phone line fail and puts Event {99} in the log.
2. System starts dialing attempts if programmed for Phone Fail report.
3. Phone line restores before Comm fail event.
4. System sends phone line fail and phone line restore reports.
If the phone line fails (as described above), but restores after a Comm Fail event:
1. System detects phone line fail and puts report in the event in the log.
2. System starts dialing attempts if programmed for Phone Fail report.
3. Dialing attempts end with Comm fail event, phone fail report is flushed.
4. System detects phone line is restored and puts restoral report in buffer.
5. System starts dialing attempts and sends phone fail restoral and Comm restoral reports.
If an alternate communication path is enabled, the control panel can send a Phone Line Fail {99} report via the
alternate communication path when a phone line fault event occurs.
• No Phone Line Supervision: If this option is enabled, the control panel does not monitor the phone line
voltage. Phone Line Fault events do not appear at keypads. The other Phone Line Fault Response options are
also disabled if No Phone Line Supervision is selected.
• Enable Supervision (System Trouble at Keypad): If this option is enabled, the keypad displays a phone
line trouble message if a phone line fault occurs as described above. To enable the keypad to sound a trouble
tone on system troubles, see Keypad # Options on page 67 for details.
• Burg Alarm & Strobe Functions, All On or Perimeter Only: If this option is enabled, the system’s burglary
alarm and strobe function as configured when the system is armed All On or Perimeter Only if a phone line
fault occurs as described above. See Output Parameters on page 107 for burglary alarm/strobe output
configuration.
• Burg Alarm & Strobe Functions, Off: If this option is enabled, the system’s burglary alarm and strobe
function as configured when the system is off (not armed) if a phone line fault occurs as described above. See
Output Parameters on page 107 for burglary alarm/strobe output configuration.