DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 42
Bosch Security Systems | 8/04 | 4998153891C
Perimeter Only Mode Delay Time
Address: 0268, 0269
Default: 0,0 (use assigned Entry Delay)
Selections: 0,0 to 15,15 (0 to 255 sec)
Making an entry in the Perimeter Only Mode Delay Time parameter creates an Entry Delay time that only
applies when the system is armed Perimeter Only.
If the system is Perimeter Only or Partial On and any armed zone is faulted (fire and 24-hour zones excluded), the
system starts a Perimeter Only Mode Entry Delay timer. It uses this Perimeter Only Mode timer for zones that are
assigned to either Entry Delay 1 or Entry Delay 2, and zones that are not assigned Entry Delay.
Setting the Perimeter Only Mode Delay Time to zero (0, 0) disables Perimeter Only Mode delay. When the
system is turned on Perimeter Only and 0,0 is entered for Perimeter Only Mode Delay Time, the armed entry
zones follow the Entry Delay assigned to them (Entry Delay 1 or Entry Delay 2).
Programming two Addresses sets the Perimeter Only Mode Delay Time. The system multiplies the number
entered in the first Address by 16 and adds that total with the number entered in the second Address. For
example, to set Perimeter Only Mode Delay Time 1 to 50 sec, you would enter 3 in the first Address (3 x 16 = 48)
and then enter 2 for the second Address (48 + 2 = 50). Use the formula below to calculate the delay time for
programming this parameter.
3 (Address 0268) x 16 = 48
+ 2 (Address 0269) = 50 (Perimeter Only Delay Time)
See Entry Delay Time 1 (2) on page 41 for a list of commonly used time settings.