Table 31: Control Panel Events and Reporting Formats (continued)
Event Event as shown in
Control Panel Log
SIA Report Contact ID
Report
Event Description Zone Types
Linked to Event
RPS
Event
Group
Status
Report
15 Cross,Cntrl,Dly
BM Burglary
Alarm Cross
Zone
134 Entry/Exit
Alarm, Delay 1 or Delay 2 Zone
Type with Cross Zone Option
selected.
11- E/E Delay 1
12- E/E Delay 2
3
16 Cross,Cntrl
BM Burglary
Alarm Cross
Zone
130 Burglary
Alarm, Follower or Instant Zone
Types with Cross Zone Option
selected.
13- Follower
14- Instant
3
17 Cross,Unverified
BG Unverified
Event Burglary
378 Cross-
zone Trouble
A fault on one non-fire zone type
with the Cross Zone Option
selected. This is not an alarm event.
any with Cross
Zone Option
3
18 Alarm Exit Error EA Exit Alarm
374 Exit Error
(zone)
Zone faulted at the end of Exit
Delay.
11- E/E Delay 1
12- E/E Delay 2
3
19 Alrm Recent Clse
CR Recent
Closing
134 Entry/Exit
Alarm event within 2 min. of
closing.
11- E/E Delay 1
12- E/E Delay 2
3
20 Alrm Recent Clse
CR Recent
Closing
130 Burglary
Alarm event within 2 min. of
closing.
10- Keyswitch
13- Follower
14- Instant
3
21 Auto On Extended
CE Closing
Extend
464 Auto-arm
Time Extended
Auto On Sked delayed one h by
user. Report follows Open/Close
routing.
10
22 Battery Low
YT System
Battery Trouble
302 Low
System Battery
Panel battery is low. 12 R S
23 Battery Missing
YM System
Battery Missing
311 Battery
Missing/Dead
Panel battery is missing. Very low,
shorted, or open batteries are
reported as missing.
12 R S
24 Rstrl Batt Low
YR System
Battery Restoral
302 Low
System Battery
Battery restoral from low battery. 12 R S
25 Rstrl Bat Missng
YR System
Battery Restoral
311 Battery
Missing/Dead
Battery Restoral from missing
battery
12 R S
26 Bypass,Fire,User FB Fire Bypass
571 Fire
bypass
Selective bypass by user, fire zone
types.
1- Fire
2- Fire with
Alarm
Verification
15
27 Bypass,Fire, RPS FB Fire Bypass
571 Fire
bypass
Selective bypass by RPS, fire zone
types.
1- Fire
2- Fire with
Alarm
Verification
28 Bypass,Ctrl,User
BB Burglary
Bypass
570
Zone/Sensor
bypass
Selective bypass by user,
controlled zone types.
10 to 15- Zone
Types
15
29 Bypass,Ctrl, RPS
BB Burglary
Bypass
570
Zone/Sensor
bypass
Selective bypass by RPS, zone
types.
10 to 15- Zone
Types
30 Bypass,24hr,User
BB Burglary
Bypass
572 24-Hr
Zone Bypass
Selective bypass by user, 24-hour
non-fire zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
31 Bypass,24hr, RPS
BB Burglary
Bypass
572 24-Hr
Zone Bypass
Selective bypass by RPS, 24-hour
non-fire zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
32 Bypass,Forced Zn
BB Burglary
Bypass
570
Zone/Sensor
bypass
Zone force armed at force arming.
10 to 15- Zone
Types
15