DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 39
Bosch Security Systems | 8/04 | 4998153891C
Open/Close Reporting Options
• Address: 0261
• Default: 3
• Selections: 0 to 15
Enter This Data Digit to Select Options
Open/Close Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Open, Close, Exit Error, or Recent Close Reports
•
Opening {89-96, 164} Reports Enabled
• • • • • • • •
Closing {42-67, 165} Reports Enabled
• • • • • • • •
Exit Error {18} Report Enabled
• • • • • • • •
Recent Closing {19-20} Reports Enabled
• • • • • • • •
This is a global parameter that affects all zones, all areas, and all PINs.
Opening and Closing reports can be restricted by area (see Area # Opening {89-96}/Closing {42-67}
Reporting Options on page 49) and by Authority Level once they are enabled and configured here.
Reporting must be enabled at the system level first (see Global Reporting Options on page 19).
• Opening Reports Enabled: If selected, this option enables Opening {89 to 96, 164} reports.
• Closing Reports Enabled: If selected, this option enables Closing {42 to 67, 165} reports.
• Exit Error: Only the Exit Error {18} report is enabled and disabled by this option. If an Entry/Exit Delay
zone (Zone Function Types 11 and 12) is violated at the end of Exit Delay, these events occur in this order:
1. Local alarm annunciation is started (keypads and alarm outputs).
2. Entry Delay starts.
3. The alarm report process begins if the system is not turned off at the end of Entry Delay. An Exit Error
{18} report is included if programmed. The Exit Error report follows the Alarm Report routing.
• Recent Closing: If this option is enabled, an Alarm Recent Closing {19 to 20} report (including the user
number) is sent for any alarm within 2 min. of the end of Exit Time.