• Relay Restoration: The status of relays after
programming or resetting the control panel might
restore automatically or require manual
restoration. All relays are turned off after the
control panel resets. The control panel checks
certain relay functions every minute and resumes
the correct state after the reset. Other relays must
be manually set to the correct state using the
Change Relay Function (COMMAND 54).
Relay functions that resume the proper state
within one min:
Alarm Bell Perimeter Fault
Summary Fire Summary Trouble
Area Armed Reset Sensors
Fire Bell AC Fail
Summary Alarm Phone Fail
Silent Alarm Summary SupBurg
Area Fault Battery Trouble
Summary Fire Tbl Communications Fail
Watch Mode Summary SupFire
Relay functions that must be reset manually
with Change Relay function (COMMAND 54):
Fail To Close Force Armed
Duress Log % Full
2.13.1 Area Relays
Each area can be assigned a unique relay number for
each of the events listed in this section.
Area
Default: 1
Selection: 1 to 4
Enter the area number you are programming.
• The D7212GV2 allows programming for
Areas 1 through 4 only.
• The D5200 Programmer allows entries
for Areas 5 through 8, but they cannot be
used on the D7212GV2.
• If Areas 5 through 8 are programmed for
the D7212GV2, the keypad displays
CALL FOR SERVICE.
A# Alarm Bell
Default: A
Selection: Blank, 1 to 24, A, B, or C
This voltage output relay activates and provides
12 VDC output when a Non-fire point (
P## Fire
is
No) assigned to this area activates an alarm.
A# Burg Time and A# Burg Pat must be
programmed in Area or Bell Parameters.
This relay activates according to the bell
pattern and remains active until the bell
time expires or a valid passcode is entered.
P## Silent Bell must be No for the bell to
ring upon alarm.
For SIA CP-01 Compliance:
Do not set
A# Alarm Bell
to blank. This feature is
required for SIA CP-01 compliance.
A# Fire Bell
Default: A
Selection: Blank, 1 to 24, A, B, or C
This voltage output relay activates and provides
12 VDC output when a Fire point (
P## Fire
is Yes)
assigned to this area activates an alarm.
Fire Time and Fire Pat must be
programmed in Bell Parameters. This relay
activates according to the bell pattern and
remains active until the bell time expires.
P## Silent Bell must be No in order for the
bell to ring upon alarm.
Although Relay C is a valid entry for A#
Fire Bell, do not program Relay C for this
entry. Use Relay A for the A# Fire Bell.