D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 11
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
2.2.1 Special Point/User Reporting
Independent Zone Control Notice: When using
Independent Zone Controls (IZC) to send
Opening/Closing Reports by point, do not duplicate
reporting independent point numbers with User ID
Reports (refer to Section 3.1 Passcode or Token Worksheet
on page 76). For example: If an IZC is connected to
Point 8, do not use User ID 8.
D6000: Opening/Closing User ID numbers are
identified at the receiver as ZONEs (same identification
as independent points).
Table 6: D6000 User IDs and Zones
User ID
Number
Zone
1 B
2 C
3 D
4 E
5 F
6 6
7 7
8 8
91 1
92 2
93 3
94 4
95 5
96 0
D6500/D6600 Receiving BFSK Format:
Opening/closing User ID numbers are identified at the
receiver as ZN (same identification as independent
points). The ZN numbers are based on the tens digit of
the User ID number. This applies only for Users 000
through 099.
DTMF Dialing
Default: Yes
Selection:
Yes or No
Yes Dials the programmed phone
number(s) using DTMF.
No Pulse dialing only.
Use dual-tone multi-frequency (DTMF) to dial the
central station receiver phone number(s) for event
reports, or to dial the remote programming software
(RPS).
Phone Supv Time
Default: Blank
Selection:
Blank or 10 to 240
Blank No phone line supervision.
10 to 240 Enter the number of seconds (in 10 sec
increments) you wish to wait before
indicating trouble. After a faulted
phone line restores, it takes the same
amount of time to start restoral
responses.
Phone line trouble responses: Keypads display
SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if
Buzz on
Fail
is Yes and
CC Trouble Tone
is Yes.
Phone, Trouble, and Restoral Events report when they
occur. They report also when a Diagnostic Report is
initiated from a keypad or by a Sked.
Alarm On Fail
Default: No
Selection:
Yes or No
Yes Generate alarm responses when a
phone line fails.
No Phone failures report as trouble
responses for Area 1 or the account
number associated with Area 1.
Phone Supv Time must be programmed to
use this feature.
Phone Failure Alarm Responses: The Alarm Bell
relay for Area 1 activates. All Phone Event messages
report as Area 1 and the account number for Area 1.