D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 22
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
RG# Primary SDI
Default: No
Selection:
Yes or No
This parameter determines if the primary destination
for Route Group 1 (2, 3, or 4) is sent to the NIM
RG# Backup SDI
Default: No
Selection:
Yes or No
This parameter determines if the backup destination
for Route Group 1 (2, 3, or 4) is sent to the NIM.
To completely disable Enhanced Routing
over an SDI path, RG# Primary SDI,
RG# Backup SDI, and Enhanced Comm
prompts must be set to No.
The poll rate entry for the backup SDI
path might need to increase because of
heavy traffic on the network or excessive
signals generated at the same time. All
Comm prompts must be set to No.
RG# Primary Pager
Default: No
Selection:
Yes or No
This parameter determines if this route group sends
events to a numeric pager. To send events to a
numeric pager, a phone number must also be
programmed in the route group’s primary destination.
If programming the control panel to dial a
numeric pager, choose its route group
carefully. Place events being sent to a
central station in a route group class with a
lower number than the numbers of the
events in the route group for the numeric
pager.
Numeric Pager Capability
The D7212GV2 Control Panel can send most events
to a numeric pager. Any time an event is generated
and routed to a numeric pager, the control panel calls
the numeric pager once for each message in the queue.
To enable the pager, program the primary phone
number and the backup phone number to the numeric
pager’s phone number in any of the four route groups.
Then select which events to route to the numeric pager
within the selected route group.
Up to four event fields can be shown in the pager
message. Refer to Figure 1.
Figure 1: Pager Display Fields
[1234-001-011-008]
1
2
3
4
1 - Account number (1234)
2 - Event policy (001)
3 - Event number (011, Fire Alarm Event)
4 - User number, point number, or relay number
(008)
The account number must contain four
numeric digits. No alpha characters (B to
F) are allowed when using the numeric
pager.