D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 64
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
If enabled in Routing, Walk Start and Walk End
Reports are sent to the central station receiver at
the beginning and end of the test.
L## Fire Test
Default: Refer to the program record sheet
Selection: Blank or E
Function No. Function Name Alternate Keystroke
12 Fiire Test [COMMAND][5][8]
Fire Walk Test all 24-hour points in the area where
this keypad is assigned.
One person can perform a Fire Walk Test without
assistance. The following features come with the Fire
Test Mode:
Battery powered control panel only. A Battery
Test runs during the whole test to ensure that the
battery capacity is capable of supporting the full
load of the control panel if AC fails.
- This test includes a 2-sec Bell Test (Fire Bell
relay) for each Fire point that is tested.
- The test ends when all points are tested or the
test times out after 20 min of no activity.
Local alarm annunciation and event printing; no
reports are sent to the central station receiver.
Automatic smoke detectors reset for all Fire points
programmed with
P## Resettable
as Yes.
D1255 Keypad displays a sequential count and the
text for the point after each point is activated and
restored.
If enabled in Routing, Walk Start and Walk End
Reports are sent to the central station receiver at
the beginning and end of the test.
A# Verify Time for Fire points that is
programmed with Yes for P## Alarm
Verify is ignored during the Fire Walk Test.
L## Send Report
Default: Refer to the program record sheet
Selection: Blank or E
Function No. Function Name Alternate Keystroke
13 Send Report [COMMAND][4][1]
or
[COMMAND][4][2]
Send a Test Report from any keypad assigned to an
area where the user has authority.
Access Control Functions
The following five functions are used to control the
doors from the keypad. These features are not
available with the D7212GV2.
L## Door Control
Default: Refer to the program record sheet
Selection: Blank or E
This feature is not available with the D7212GV2.
Keep the default setting.
L## Cycle Door
Default: Refer to the program record sheet
Selection: Blank or E
This feature is not available with the D7212GV2.
Keep the default setting.
L## Unlock Door
Default: Refer to the program record sheet
Selection: Blank or E
This feature is not available with the D7212GV2.
Keep the default setting.
L## Secure Door
Default: Refer to the program record sheet
Selection: Blank or E
This feature is not available with the D7212GV2.
Keep the default setting.
L## Access Ctl Lvl
Default: Refer to the program record sheet
Selection: Blank or E
This feature is not available with the D7212GV2.
Keep the default setting.