DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 86
Bosch Security Systems | 1/05| 4998154963B
For example, use the following steps to program Output Function 4 to follow Zone 1 when the zone is shorted and
the control panel is armed.
1. Enter “*3” (see Table 124) in Data Digit 1 of Program Address 1 (2781).
This option programs the output function to follow a selected zone in an input/output cross matrix.
2. Enter “1” (see Table 128) in Data Digit 2 of Program Address 1 (2781).
This option programs the output function to activate when the zone it follows is shorted and the control panel
is armed.
3. Enter “0” in Data Digit 1 of Program Address 2 (2782), and “1” in Data Digit 2 of Program Address 2 to
assign this output function to Zone 1. The entries made in Program Address 2 are hex values (see Table 113).
Output Function 4 is now assigned to follow Zone 1. Any output assigned to Output Function 4 activates when
Zone 1 is shorted and the control panel is armed.
Follow Two Zones
Data Digit 1 Options *4 and *5 program an output function to follow two zones in an input/output cross matrix.
Option *4: Follow two zones when EITHER zone changes state.
Option *5: Follow two zones when BOTH zone changes state.
This option requires the use of three program addresses:
Program Address 1: Enter the output function option in Data Digit 1 (see Table 116); enter the zone/control
panel state option in Data Digit 2 (see Table 128).
Program Address 2: Enter the first zone number in Data Digits 1 and 2 using hex values (see Table 113).
Program Address 3: Enter the second zone number in Data Digits 1 and 2 using hex values (see Table 113).
See Table 116 for output function options. See Table 126 for output function numbers/program addresses.