DS7400XiV4-EXP | Reference Guide | 7. Reference Materials EN | 113
Bosch Security Systems | 1/05| 4998154963B
Water Flow Zone: This is a zone programmed to
operate like a Fire Zone, but is specifically intended for
water flow switches.
• An optional retard timer can be programmed to
compensate for changes in water pressure. If the
timer is used, the water flow zone must be activated
for the complete time period; an alarm will be
initiated at the end of the timer period.
• The maximum combined water flow delay of the
control panel and the device must not exceed two
minutes.
Any zone can be a water flow zone, but
only zones 1 through 4 may be
programmed as delayed water flow zones.
Supervisory Zone: This is a zone programmed to
accommodate shut-off valves.
• It will indicate a supervisory condition at the
keypads when activated.
7.2.3 Zone Programming
Zone: A Zone is an input to the DS7400Xi
Control/Communicator.
• There are eight hardwired zones on the main circuit
board.
• Additional zones may be added by using the
DS7433 (8 zone expansion module), the DS7430
(multiplex loop module), and/or other modules.
Single Zone Input: This is an individual zone such as
the on-board zones and multiplex contact zones.
Multiple Zone Input: This is a zone connected to one
of the 8-Input Modules (DS7432E or DS7433) or to a
Dual Zone Module (DS7460i).
• The inputs are programmed separately (see the
separate Programming Addresses Worksheet, P/N:
29802).
• When using the Dual Zone Module (DS7460), loop
A is always programmed as an odd numbered
program address (ending in 1, 3, 5, 7, or 9). Loop B
is the even numbered program address that follows
loop A.
DS7465i: This is the input zone or the output relay on a
DS7465i. The odd numbered zone is programmed for
the input zone function and the even numbered zone is
programmed for the output function.
Multiplex Smoke: This is a multiplexed input zone
(zones 9-248) that is used with a MX250 or MX280
series smoke detector. This zone must have a Zone
Function of Fire Zone and Trouble on Open applied
to the multiplex smoke zone.
Smoke alarm: This must be the odd-numbered zone
of the zone pair required for these devices. The zone
must be programmed with a zone function that is set
for Fire Zone and Trouble on Open.
7.2.4 Output Programming
Latch on Any Zone Alarm: This is an output
programmed to activate upon any zone alarm
(including invisible zones) and will latch until the
system has been disarmed.
• If this output is programmed to respond only to a
fire zone, it will remain latched until the fire reset
command is performed.
ON during Entry Pre-Alert: This is an output
programmed to activate when an entry/exit zone is
violated while the system is armed.
• It will remain activated until the system is
disarmed, or until the entry delay time has
expired.
ON for 10 seconds after [PIN][System Reset] is
entered: This is an output programmed to activate for
10 seconds after the fire reset command is entered at
the keypad or if a Fire Zone with Verification
activates.
• This output is intended to be used to power 4-wire
smoke detectors or any other device that requires
a power interruption to reset an alarm condition.
When Programmable Output 2 is
programmed this way, it will normally
supply auxiliary power and will turn OFF for
10 seconds when the fire reset command
is entered.
ON when System is Armed: This is an output
programmed to activate when the system is armed.
• It will remain activated until the system is
disarmed.