PI -- 34.65dProduct Information MAGIC.SENS -- Product r ange
Page 37 of 42
BDL--4998121218
A23.en /09.02.2007
ST--FIR/ PRM1 / deh
11.5. Test procedure for MAGIC.SENS OC 310 GLT
With the OC 310 you must first test the opticalunit with the test aerosol. After triggering
the O unit, the detector must be r eset. T hus the CO sensor is switched into
maintenance mode for 15 m inutes and it can then be tested. Since the aerosol test for
the detectors works like a disturbance signal, (very large signal with very quick
increase), the signal evaluation for disturbance variable is brought to bear and the
alarm occurs only after approximately one minute.
D Position detector testers for smoke detectors on the OC 310 GLT.
D Spray aerosol (1 to 2 seconds).
. Do not remove test device from the detector; the O unit triggers only
approximately 60 seconds after the application of the test aerosol.
D Reset detector.
. Thus the detector is switched into maintenance mode.
D Place CO gas bottle in the test device.
D Position test device on the detector.
D Apply CO gas for
1
/
2
to 1 second.
. Th e C sensor triggers after approximately 20 seconds.
11.6. Inspection procedure for OT 300 GLT / O 300 GLT
D Position detector testers for smoke detectors on the OT 300 GLT / O 300 GLT.
D Spray aerosol (1 to 2 seconds).
. Do not remove test device from the detector; the O unit triggers only
approximately 30 seconds after the application of the test aerosol.
D Reset detector.
. Thus the detector is switched into maintenance mode.
D The temperature sensor of the OT is tested with the test device for heat detectors.