PI -- 34.65dProduct Information MAGIC.SENS -- Product range
Page 10 of 42
BDL--4
998121218
A23.en /0
9.02.2007
ST--F
IR/ PRM1 / deh
4. Programming
Programming is setting a LSN detector to the desired operating mode.
Pro
gramming is carried out with the >WinPara< software using a PC or laptop connected
to t
he fire panel.
All sensor signals are analyzed continually by the internal evaluation electronics and
are linked with each other via an inbuilt microprocessor.
The d
etectors OTC 410 LSN OC 410 LSN and OT 400 E LSN are programmed by
specifying the o
peration location (e.g. computer room, office, large kitchen).
The sele
ction of the operation location determines the optimal characteristic diagram
for fire a
nd disturbance variable evaluation.
With low sensitivity of the o
ptical sensor in the OTC 410 LSN, the detector only triggers
if s
moke and also an increase of the CO concentration or the temperature is detected.
With the ty
pes OTC 410 LSN and OT 400 E LSN, the operating mode can be changed.
Th
at is, individual sensors can be switched off:
-- Sw
itch to optical (sensitivity O unit = low, T unit = switched off)
-- Sw
itchover to thermo--differential (sensitivity T unit = A2R, O unit = switched off)
-- Sw
itchover to thermo--maximum (sensitivity T unit = A2S, O unit = switched off)
With p
urely optical detectors O 400 E LSN, the sensitivity of the optical sensors can
be s
et on 3 levels. Depending on the operation location, the optical sensor in the
detector is th
us adjusted to the environmental conditions.
For fire re
cognition, the optical detector uses the temporal behavior of the fire variables
that deviates significantly from the temporal behavior of disturbance variables and
also f
rom the time behavior of a detector test with aerosol. Depending on the sensitivity
set, t
herefore there are also different trigger times when testing with a test aerosol,
outside of main
tenance operation (10s to max 60s).
The thermal detector T 400 E LSN is programmed by taking into account the ambient
temperature a
nd installation height with the selection of the sensitivity class.
Pro
gramming of the optical, thermal, and chemical detector and the linking of all detectors
via al
gorithms significantly increases the detection ability and security against false alarms.