PI -- 34.65dProduct Information MAGIC.SENS -- Product r ange
Page 33 of 42
BDL--4998121218
A23.en /09.02.2007
ST--FIR/ PRM1 / deh
11. Maintenance and service
For maintenance and inspection work on danger detector systems, in Germany
the regulations of DIN VDE 0833 apply, which refer to the maintenance interval
according to the manufacturers instructions.
D Maintenance and inspection work should be carried out regularly and by trained
personnel.
D BOSCH ST recommends a functional and visual inspection at least once a year.
Testing
De tec tor type
O T OT OC OTC
Check of the display LED x x x x x
Visual check of the fastening x x x x x
Visual check for damage x x x x x
Checking that the monitoring area is not limited x x x x x
T riggering with hot air -- x x -- x
T riggering with Solo A3--001 testing gas x -- x x x
T riggering with CO testing gas -- -- -- x x
D Multisensor detectors with C--sensors must be exchanged every 5 years.
. OTC 410 L SN / OC 410 L SN:
Depending on the lifespan of the gas sensor, the detector OTC 410 LSN and OC
410LSN switches the C--sensors off after 5 years of operation. On the central unit,
the detector in question is displayed with “EMERGENCY OPERATION” and it
continues to function as an OT or O detector.
The detector should be exchanged immediately in order to be able to keep using
the higher detection security of the OTC and OC.
. OC 310 GLT:
Depending on the lifespan of the gas sensor, with the OC 310 GLT the C--sensor
is switched off after approximately 5 years of operation; the detector continues to
function as an O detector.
Depending on the system, there is no report to the centr al unit and the switching--off
of the C unit is only noticed when the detectors are tested. Therefore the OC 310
should be exchanged in timely fashion before 5 years of operation have e lapsed.
D Optical fire detectors (smoke detectors) should, depending on the
environmental conditions, b e cleaned and exchanged every 4 -- 6 years.
. In especial ly dusty environments, cleaning and exchange may be necessary earlier!