PI -- 34.65dProduct Information MAGIC.SENS -- Product r ange
Page 12 of 42
BDL--4998121218
A23.en /09.02.2007
ST--FIR/ PRM1 / deh
4.3. MAGIC.SENS OT 400 E LSN
Sensitivity
Operation locations that can be selected in the
>WinPara< programming software
Detector type
T
max
--uni
t
O--unit
Theaters / Concert Halls combined
O+T
max
+T
diff
high (A2) mediu
m
W arehouse with vehicle traffic combined
O+T
max
+T
diff
low (B) low
Office (smokers) / W aiting room / Restaurant /
Conference room
combined
O+T
max
+T
diff
high (A2) low
Conference room / Waiting room / Exhibition hall combined
O+T
max
+T
diff
high (A2) low
Office (no traffic) combined
O+T
max
+T
diff
high (A2) high
School / Kindergarten combined
O+T
max
+T
diff
high (A2) mediu
m
Garage T
max
+T
diff
high (A2) --
Kitchen / Casino / Restaurant (during operation) T
max
low (B) --
Production Facilities combined
O+T
max
+T
diff
low (B) low
Computer room combined
O+T
max
+T
diff
high (A2) high
High--board warehouse without vehicle traffic with
combustion motors
combined
O+T
max
+T
diff
low (B) high
Office (daily operation) combined
O+T
max
+T
diff
low (B) mediu
m
4.4. MAGIC.SENS O 400 E LSN
O
eration location and recommended settin
in the Sensitivit
>WinPara< programming software
O--unit
Theaters / Concert Halls medium
W arehouse with vehicle traffic low
Office (smokers) / W aiting room / Restaurant / Conference room low
Conference room / Waiting room / Exhibition hall low
Office (no traffic) high
School / Kindergarten medium
Production Facilities low
Computer room high
High--board warehouse without vehicle traffic with combustion motors high
Office (daily operation) medium
For fire detection, the purely optical detector also evaluates the time
behavior of the fire characteristics that differs significantly from the time
behavior of characteristics during a detector test. Depending on the
sensitivi ty set, therefore there are also different trigger times when testing
with a test aerosol, outside of maintenance operation (10s to max 60s).