Bosch Alarm Panel Interface Manual
Revision 1.4
2.1 Physically Connecting to the Alarm Panel
STEP 1: Install and program the Alarm Panel according to the Manufacturer’s Instruction
The Alarm Panel should be installed and fully configured before connecting to System Galaxy.
STEP 2: Connect the Alarm Panel to the System Galaxy Communication Server/PC
Bosch 9000/7000 Series alarm panels can connect to the SG Communication PC by three
possible choices described below. Note that these include parameters required for System
Galaxy.
The ‘SG Communication Server (PC) is defined as the computer running the GCS Services (including
the Alarm Panel service).
a) (CHOICE A) Ethernet Device (most common) DX4020 Module: installer must set up the
module including the following known requirements:
Use wiring info in Bosch install documentation
DIP switch settings 1 thru 6 and 8 = down/off and 7 = up/on
a. Flow control = none
b. UDP datagram = disable ( to use TCPIP)
c. telnet port = 9999
d. Set connect mode to “C0” (C, zero) instead of “CC”;
Supports encryption - special configuration info in the Bosch manuals.
This is set at the
module via telnet and must be set on the System Galaxy end in the Alarm Panel Service screen.
Whatever is set at DX2040 module must match the setting in the Alarm Panel Service. See Section 8
for how to configure encryption at the Alarm Panel Service.
key length = 128 (default) ; must be zero if not used.
must specify a key value: the key value is a 16 digit hex code; must be blank if not used.
Example: ‘01020304050607080910111213141516’ is an example of a 16 digit hex code,
which is actually 32 characters long; a hex digit is made of 2 characters. Valid hex
characters are: 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F. Therefore a hex value of ‘01’
= 1 and ‘0A’ = 10 when converted to decimal value.
b) (CHOICE B) Direct connect using RS 232 Connection Module such as the Model DX 4010i:
t
he RS-232 module provides serial connection to System Galaxy Communication Server (PC). The
Communication Server is defined as the PC where the main GCS Services reside. See Figure A for a
diagram of the Alarm Panel Interface depicting services.
Wiring info is in the Bosch Install documentation for com to panel
DIP Switch settings are 1,2,3,4 = UP and 5,6,7,8 = DOWN
9600 Baud, no parity, 8 bit, 1 stop bit
Uses DB9 RS232 cable to connect to PC com port
Pin Out for RS-232 Cable
DB9 female DB9 female
2 3
3 2
5 5
c) (
CHOICE C) Direct connect (as above) with Lantronix: IP on the SG COMM SIDE TO
LANTRONIX
Configure Lantronix device the same as with
Network Bridge for a Remote Primary 508
panel. See the Lantronix manual for configuration information.