8.3.3 How to connect to the Alarm Panel
The GCS Alarm Panel Service reads the alarm panel configuration from the SG database and begins
making attempts to auto-connect to the panel at least 60 seconds after the configuration is saved.
Part 4: Connect to the Alarm Panel manually as well as view/edit connection properties: The
Alarm Panel Connections tab shows an IP connection for each
alarm panel that has been configured in
System Galaxy. The status (connected or disconnected) is displayed (see fig. 11a).
a) Auto-Connect: the Alarm Panel service should automatically connect to the panel once the
configuration is saved in the SG Database. The auto-connect option defaults to “on” and can be
edited for each individual panel connection from the Service Configuration window (see Sect.
8.3.4).
NOTE: The ability to connect to a panel depends on several things:
The alarm panel must be properly connection to the SG Communication Server (PC).
The Alarm Panel must be registered and correctly configured in System Galaxy.
Both the DBWriter Service and Alarm Panel Service must be running.
b) User can manually connect and disconnect from the alarm panel by right-clicking the
connection status and getting a shortcut menu.
NOTE: The short menu also allows user to open the Connection Properties
where the settings to
automatically connect to panel can be enabled or disabled. User can also edit the Connection Settings
and configure Encryption from the Connection Properties screen. See Section 8.3.4 for details.
FIG 11a: Alarm Panel Service screen/Connecting to the Alarm Panel (cropped)
Right-click the panel status and
Select the desired command
` Connect/Disconnect - user can manually connect/disconnect the selected panel.
` Ping/Telnet – opens a DOS window and executes a ping/telnet command to the IP Address of the
selected panel. (Only for panels using TCP/IP connections)
` Properties – opens the Connection Properties screen, allowing user to change the connection
settings for the selected panel. See the following section on Managing Connection Properties for
details on the properties fields and Setting Encryption.