K2200 Series | Installation Guide | 5.0 Installation Details EN | 28
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
In the table at the right record a current consumption for each device fitted:
Table 12: Total Reader Channel Current
Channel
1234
Reader Current 1
35 mA (see Note 1)
Reader Current 2
100 mA (see Note 2)
Wiegand\Magstripe
Reader 50 mA
Module Relays
30 mA
Total: Must not exceed
200 mA/channel
Note 1:
Reader Current 1 applies to the readers with flying
leads
(15 mA idle, 35 mA active).
Note 2:
Reader Current 2 applies to the readers with screw
terminals as well as the panel mount reader.
Note 3:
When using a reader combiner, you should include the
current of the combiner in its column plus the total
current for both readers in the reader column.
Note 4:
Only include a value for the reader current if the
Wiegand reader is powered from the Wiegand interface
unit’s 5 VDC output or the 18 VDC reader supply
Note 5:
Include 40 mA for each AEM that is connected to a
reader channel.
Determining Total Power
The door controller itself consumes 1 A before the
addition of any readers or locks.
For each 100 mA of reader channel current, as
determined above, an additional 150 mA should be
allowed. This is due to several factors involved in the
generation of the 18 VDC VDC supply.
Table 13: Determining Total Power
Door Controller 1 A
A
A
Total: A
The above figures are all stated in Amps, 1 A = 1000
mA.
Alarm Controller
The capacity of the battery required should be
calculated based on:
• The current consumption of the alarm controller
(1 A).
• The current consumption of the devices (AEMs,
detectors, etc.) attached to the controller, up to a
maximum of 800 mA
The length of time the system should operate without
mains power.
Note:
Each AEM can be powered from the controller or via a
separate power supply. The current drawn by each
AEM is a maximum of 40 mA.