Occasionally abnormal
communication in use of
Contact ID/personal
telephone alarm.
Extension system is used
in the telephone
network.
The telephone network
support ADSL as well.
Add dial delay in
programming.
Connect the system after
the ADSL filter.
No response from keypad and
alarm siren (disabled) when
an alarm is triggered by the
zone.
The zone silent alarm is
enabled.
Disable the zone silent
alarm.
The control panel cannot
send any reports
(programmed to send reports
to receiver).
The transmission format
of the receiver is
programmed to 0 = not
used.
Program the
transmission format of
the receiver to 1 or 3.
A-LINK cannot be connected
with ITS- DX4020-G.
The parameters of ITS-
DX4020-G are not
properly set.
Recommend to set the
parameter ACK TIMEOUT
of ITS-DX4020-G to the
maximum (600) and set
TRANSMIT BUFFER LIFE
TIME to the maximum
(120).
AMAX panel 4000 / AMAX panel 4000
EN
Troubleshooting | en 169
Bosch Sicherheitsysteme GmbH Installation Guide 2013.07 | 03 | F.01U.267.112