wLSN | Reference Guide | 13.0 wLSN Smoke Detector
Bosch Security Systems, Inc. | 3/07 | F01U009440-01 45
13.3 Sensitivity Test
Test mode is seen by the control panel as a test. It does
not send an alarm.
The detector includes a Sensitivity Level Test mode for
determining the detector’s sensitivity:
1. Press and hold the Test/Silence button for 4 sec. The LED
flashes 1 to 9 times.
2. Count the number of LED flashes and use Table 20 to
determine the status of the detector’s sensitivity and the
action to take.
Table 20: Smoke Detector Sensitivity Conditions
Flashes Action Recommended
1 Self-diagnostics failure. Return device for service or replacement.
2 to 3
Device is becoming insensitive. Clean the detector and re-test. If
error persists, replace the detector.
4 to 7 Detector is within normal sensitivity range.
8 to 9
Device is becoming too sensitive. Confirm that the smoke
chamber is snapped down securely. Clean the sensor and re-test.
13.4 Test/Silence Button
Refer to Figure 15 on page 44.
• Testing: Press the Test/Silence button for 4 sec. The detector
performs a Sounder test and a Sensitivity test.
• Silence alarm: Press to silence the sounder during an alarm.
After a few minutes, the sounder and alarm resume if smoke is
still present.