PROFIBUS-DP raw
Telegram Length
The telegram length is set in the PROFIBUS configuration. Specify the
same value in the PROFIBUS programming software.
Floating Point Format
Enter the interpretation form for floating point numbers. This is also the
setting for a timer and counter in the Siemens DCS format.
Byte Order
Specify the byte order for word and double-word addresses. (Siemens
= High-Low, Bosch = Low-High)
Configurable
Values
Default Value
8 bytes to 32 bytes 20 bytes
Fig. 6-187: Telegram length, PROFIBUS-DP
Configurable
Values
Default Value
Siemens Format
IEEE Format X
Fig. 6-188: Floating point format, PROFIBUS-DP
Configurable
Values
Default Value
Low-High X
High-Low
Fig. 6-189: Byte order, PROFIBUS-DP