R911305038 / 01 | Rexroth VCP-Operating Concept Electric Drives and Controls | Bosch Rexroth AG 6-67
Bosch BUEP19E
6.5.4 Error Messages
Error messages are displayed on the operating device along with a
code and subcode. Error messages are composed as follows.
Communication Error
Code XXXXX
Subcode XXXXX
Retries XXXXX
Code Subcode Error Type Possible Cause
1 1 Slave not ready Wrong baud rate or cable
defective
3 Error in protocol frame
5 CRC error
6 Wrong parity
10 No cyclic data defined
16 Receive buffer overrun
Bosch-Specific Error Messages
1 50 No connection set-up
51 Wrong acknowledgement during connection set-
up
52 Wrong acknowledgement after sending informa-
tion block
Wrong block check set, PG
uses LRC8. The first peri-
pheral participant determi-
nes the block check used !
53 No response telegram
54 Timeout - No response telegram
55 Block time exceeded
56 No acknowledgement
57 EOT - Aborted by controller
2 58 Incorrect number of data received Check if the mask, in which
the error occured, contains
a variable with an odd num-
ber of bytes which acces-
ses a word address or a
double-word address.
Fig. 6-103: Error Messages for Bosch BUEP19E