PRE-
INSTALLATION
INSTALLATION INSTRUCTIONS
7
TERMINAL OUTLET POSITIONS
8 718 682 335b (09.2008)
Flue clearances must be at least
300mm from the ground. Terminal
guards must be fitted if the flue is less
than 2 metres from the ground or if a
person could come into contact with
the flue terminal.
1,200mm from an opening on the same
wall (ie: door or window leading into a
dwelling) in a carport with both sides
open,to prevent the build up of
combustion products.
600mm to a surface facing a terminal.
Clearance no less than 200mm
from the lowest point of the
balcony or overhang
The flue cannot be
lower than 1000mm
from the top of a light
well due to the build
up of combustion
products
300mm to an
internal or
external corner
1500mm between a vertical flue
terminal and a window
or dormer window
400mm from a pitched roof
or in regions with heavy
snow fall 500mm
2000mm below a Velux window,
600mm above or to either side
of the Velux window
mm
300mm
1500mm
300mm
Window
RAINPIPE
300mm above,
below and either
side of an opening
door, air vent or
opening window
1200mm between terminals
facing each other
1200mm
1500mm
400mm
DORMER
WINDOW
VELUX WINDOW
300mm
00mm
8 716 115 089a
NOTE:
Installations in carports
are not recommended
300mm
300mm