D7212GV2 | Operation and Installation Guide | 9.0 Off-Board Points
38 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
Figure 16: Program Record Sheet
9.3.8 POPIT Labels
D7212GV2 off-board points are numbered 9 to 40.
Two sheets of peel-off POPIT labels are supplied with
the D8125 POPEX Module. Use the sheet marked
“Bank1” for Points 9 to 40.
Each label has two parts. Place the smaller part, with
only the point number, on the chip. Place the larger
part, with the switch settings, on the base of the POPIT.
Set the switches and cover the POPIT.
Do not program two POPITs for the same point
number. After programming all the points, perform a
Service Walk Test. Refer to Section 4.10 Service Walk
Test on page 19. If a point does not test, check the
programming for a duplicated address.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, missing and
extra point conditions might occur. If the same point
number is assigned to two or more POPITs or
OctoPOPITs, none of the points with that number test
correctly. Refer to Section 9.1 Point (Zonex) Bus:
D7212GV2 Terminals on page 33.
9.4 D8128D OctoPOPIT Module
Modules D8128, D8128A, or D8128B are
incompatible with the D9412GV2 or
D7412GV2. Use only the D8128D
OctoPOPIT Module. Using Modules D8128,
D8128A, or D8128B can cause intermittent
Missing and Restoral Reports.
9.4.1 Description
The D8128D OctoPOPIT Module combines the
functions of the D8125 POPEX Module and the
D8127/D9127 POPIT Modules to provide eight off-
board points in a single module. You can wire both
D8128D OctoPOPIT and D8125 POPEX Modules in
parallel to the Zonex bus terminals on the same control
panel.
Review Section 6.0 Power Outputs on page 25 to ensure
that there is enough power for the OctoPOPITs and
other powered devices that will be connected to the
system.
Up to four D8128Ds can be connected to the
D7212GV2 Control Panel (three points can be used on
the last OctoPOPIT).
9.4.2 Listings
The D8128D OctoPOPIT Module is UL Listed for
Local or Police Connected Burglary Alarm, Central
Station Burglary Alarm, Household Burglary Alarm
applications, and commercial fire applications (UL 864
and NFPA 72).