D9412GV4/D7412GV4/D7212GV4 Reporting Format Definitions | en 23
Bosch Security Systems, Inc. Quick Reference Guide F01U215242 | 01 | 2011.10
(NEW) DNS Failure Restore
RPS
NsB01 Nrg8/pi099YK Communication Trouble
3 350 00
1
zzz
(NEW) Equipment Fail
(SDI2 only)
TsD29 NIA001 System Peripheral Trouble
1 330 00
1
zzz
(NEW) Equipment Restore
(SDI2 only)
RsD29 NIR001 System Peripheral Trouble
Restore
3 330 00
1
zzz
Event Log Overflow AsD01 NJO Event Log Overflow 1 624 00 000
Event Log Threshold has been
reached
TsD01 NJL Event Log 90% Full 1 623 00 000
Extend Close Time by Area TsD26 Nria/idiii/
tihhmmCE
Auto-arm Time Extended 1 464 aa uuu
Extra Point Tsppp NriaXEppp Maintenance Alert 1 393 aa ppp
Fail To Close by Area TsssE NriaCI Failed to Close 1 454 aa 000
Fail To Open by Area TsssE NriaOI Failed to Open 1 453 aa 000
Fire Alarm Fsppp NriaFAppp Fire 1 110 aa ppp
Fire Cancel \siii Nria/idiiiFC Cancel 1 406 aa uuu
Fire Missing Msppp NriaFYppp Fire Trouble 1 373 aa ppp
Fire Restoral from Alarm Hssppp NriaFHppp Fire 3 110 aa ppp
Fire Restoral from Trouble Hsppp NriaFJppp Fire Trouble 3 373 aa ppp
Fire Supervision Esppp NriaFSppp Fire Supervisory 1 200 aa ppp
Fire Supervision from Restore Esppp NriaFVppp Fire Supervisory 3 200 aa ppp
Fire Trouble Gssppp NriaFTppp Fire Trouble 1 373 aa ppp
Fire Walk Test End RsssF Nria/idiiiFK Fire Test 3 604 aa uuu
Fire Walk Test Start TsssF Nria/idiiiFI Fire Test 1 604 aa uuu
Force Armed Perimeter Delay Csiii Nria/idiiiNF Partial Arm 3 456 aa uuu
Force Armed Perimeter Instant Csiii Nria/idiiiNF Partial Arm 3 456 aa uuu
Forced Close Early by Area Csiii Nria/idiiiCF Early O/C 3 451 aa uuu
Forced Close Late by Area Csiii Nria/idiiiCF Late O/C 3 452 aa uuu
Forced Closing by Area Csiii Nria/idiiiCF O/C by user 3 401 aa uuu
Forced Point Tsppp NriaXWppp Zone/Sensor Bypass 1 570 aa ppp
Invalid local access detected TsF01 NLU Unsuccessful access 1 413 00 000
(NEW) IP Address Error TsssD NET System Peripheral Trouble
1 330 00
1
zzz
(NEW) IP Address Error
Restore
RsssD NER System Peripheral Trouble
Restore
3 330 00
1
zzz
Low battery on a wireless
point
Tsppp NriaXTppp RF Low Battery 1 384 aa ppp
Low battery restore on a
wireless point
Rsppp NriaXRppp RF Low Battery 3 384 aa ppp
Missing Alarm Msppp NriaUZppp General Alarm 1 140 aa ppp
Missing Fire Supervision GMsppp NriaFZppp Fire Trouble 1 200 aa ppp
Missing Supervision MTsppp NriaBZppp Loss of Supervision - RPM 1 382 aa ppp
Missing Trouble Vsppp NriaUYppp Loss of Supervision - RPM 1 382 aa ppp
(NEW) Network Cable
Disconnected
TsssD NET System Peripheral Trouble
1 330 00
1
zzz
(NEW) Network Cable
Connected
RsssD NER System Peripheral Trouble
Restore
3 330 00
1
zzz
Non- Fire Cancel Alarm \siii Nria/idiiiBC Cancel 1 406 aa uuu
Normal start-up of the control
panel
NsD14 NRR System Reset 1 305 00 000
(NEW) Opening by Account OSiii NidiiiOP O/C by account 1 401 00 uuu
Modem IIIa
2
Event Modem IIIa
2
Code
D6500 Mode
Modem IIIa
2
Code
Bosch SIA Mode
Contact ID Event Contact ID
Code
1