8 en | System Overview Access Control Interface Module
F.01U.215.244 | 05 | 2012.06 Installation and Operation Guide Bosch Security Systems, Inc.
Programming REX Shunt Only and RTE Shunt Only allows you to initiate only the shunt and
buzz when the [RTE] or [REX] inputs are shorted. This eliminates the need for a strike and
would be used in applications where a push bar is used to open the door.
It is advisable to assign a point number to the device used to activate the [RTE] and [REX]
inputs, such as an infrared with addressable ZONEX. This ensures that the device is
supervised.
2.1.4 Reader (Connections)
LED. Common upon card read response and strike activation. Sink up to 35 mA from 5-14 VDC
source. Output impedance ia 180Ω.
Buzzer output. Common upon strike activation. Sink up to 35 mA from 5-14 VDC source.
Output impedance is 100Ω.
+5 VDC readers. Power out to 5.2 VDC card reader. V out 5 V +/- .25 V for 20 to 140 mA load,
150 mA maximum continuous.
DATA 0. Data 0 from card reader. High impedance pull up to +/-5.2 V.
DATA 1. Data 1 input from card reader. High impedance pull up to +/-5.2 V.
2.1.5 SDI (Connections)
PWR. Provides power to the interface module and buzzer.
A PANEL DATA. Transports data communications between the interface module and the
security panel.
B PANEL DATA. Transports data communications between the interface module and the
security panel.
COM (Common). Provides electrical common between the interface module and the power
source.
2.1.6 Functions
Normal Door Sequence. The Normal Door Sequence of the interface module is initiated by a
valid access granted (User ID) or door request [RTE/REX]. This initiates the strike, shunt and
buzz time to activate the strike, shunt the point, and create an event reporting the door
sequence has begun.
When the door is held open past the normal door sequence time, an extended door sequence
time is initiated. This extended time extends the shunt and re-activates the buzzer. If
programmed, CLOSE DOOR # will display at the control center assigned to the door. The
normal door sequence will not activate if the interlock point is in an off normal (open or short)
condition.
The Interlock Point can be assigned to multiple door controllers. This is useful for applications
that require doors to not activate when a point is faulted until the interlock point is normal.
Door States. There are four door states for the interface module. These door states can be
controlled through the control center, the Remote Programming System (RPS), scheduled
events (Skeds) and automatic programmable functions in the interface module parameters.