Stainless Steel - Concentric Vent / Air Intake Kit Installation Manual | 10.2009 Technical specications are subject to change without prior notice
| 7
Installation Manual
* For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be ind
icated:
a) A minimum clearance value determined by testing
in accordance with section 2.20, or;
b) A reference to the following footnote:
“Clearance in accordance with local installation co
des and the requirements of the gas supplier.”
Canadian installations
1)
U.S. installations
2)
A Clearance above grade, veranda, porch, deck or balc
.ni 21
.ni
21
yno
B
ni 63denepo eb yam taht rood ro wodniw ot ecnaraelC
.ni 21.
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffit located above the vent
terminator within a horizontal distance of 2 feet (
61cm) from the
center line of the terminator
* *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner * *
H Clearance to each side of center line extended abov
e meter/
regulator assembly
36 in. within a height 15 feet above
meter/ regulator assembly
*
I Clearance to service regulator vent outlet 36 in. *
J Clearance to non-mechanical air supply inlet to bui
lding or the
combustion air inlet to any other application
.ni 21.ni 63
K Clearance to mechanical air supply inlet teef 01 nihtiw fi evoba .ni 63.ni 27
horizontally
L Clearance above paved sidewalk or paved driveway lo
cated on
public property
84 in.
3)
*
M ni 21ynoclab ro kced hcrop ,adnarev rednu ecnaraelC .
4)
*
1) In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2) In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
3) A vent shall not terminate directly above a sidewalk or paved driveway that is located between two s
ingle family dwellings and serves both dwellings.
4) Permitted only if veranda, porch, deck or balcony
is fully open on a minimum of two sides beneath th
e floor.
Fig. 7 Required direct vent terminal clearances (twin pipe / concentric penetration)