Water to Air Operation General Description The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured with the Wate

Página 3

Inputs  RS Room temperature sensor (Rnet)  RS Room temperature sensor Set point adjust (Rnet)  RS Room temperature sensor Occupancy overr

Página 4 - The Zone Controller

Status  Cooling/Heating control status  Cooling/Heating percentage (0-100%)  Room temperature  Discharge air temperature  Leaving water t

Página 5 - Specifications

13 Sequence of Operation Run Conditions: The unit will run according to a user definable time schedule, dry contact (physical digital input number 1

Página 6 - Figure 3 - Power LEDs

Zone Temperature The occupant will be able to see the zone temperature on the sensor LCD display in addition the user will be able to see other para

Página 7 - DIP and Rotary Switches

Freeze Protection: The unit shall shut down and generate an alarm upon receiving a freezestat status. Fan: Constant Volume In the occupied mode,

Página 8 - Jumpers and settings

Modulating Re-Heat Valve: This valve is an analog device and has the capability to modulate the amount of hot gas that is allowed through the re-he

Página 9 - LonWorks® card option

The heating will be enabled whenever:  The fan output is on.  AND the reversing valve is in heat mode (de-energized). The cooling will be enable

Página 10 - Water to Air Operation

The controller will only allow supplemental heating if the unit is configured to allow this operation, units equipped with hot ga

Página 11 - Outputs

Single Outside Air Temperature (OAT) Reset: OAT> OAT Reset °F (adj.): Controller will initiate cooling call to run compressors and modulat

Página 12

Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:...

Página 13 - Sequence of Operation

20 Controller will command the unit to run full mechanical cooling operation (on units with more than two compressors please check with

Página 14

Figure 12 - Typical water to air applications – Water to Air Standard 21

Página 15

Figure 13 -Typical water to air applications – Water to Air with Hot Gas Re-Heat 22

Página 16 - Filter:

Figure 14 - Typical water to air applications – Water to Air with CO2 and OA Damper 23

Página 17 - Reversing valve:

Figure 15 – Typical water to air application – Discharge Air Control with Modulating Reheat Valves 24

Página 19

Figure 16 - Typical water to air integration points list 26

Página 20 - UPM Fault Monitor:

27 Water to Water Operation General Description The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured with the

Página 21

28 Control & Status Parameters and Alarms Status and Control  BACview occupancy schedule  System control: Schedule, Manual ON, BAS or DI

Página 22

29 Sequence of Operation Run Conditions: The unit will run according to a user definable time schedule, dry contact (physical digital input number

Página 23

Pump Control (optional)...31 Pump Runtime Alarm:...31 Load

Página 24

30 Auto Cool:  Chageover Temperature > Changeover Setpoint + Change over dead Band Auto Heat:  Chageover Temperature < Changeover Setpoi

Página 25

31 Lead - Lag Compressor operation NOTE: This feature is only available on two stage systems. The unit will alternate the compressors by using Lead

Página 26

32 Load Water (Entering) Temperature: The controller will monitor the entering load water temperature which is located at entering side of coil. Al

Página 27 - General Description

Figure 17 - Typical water to water applications – Water to Water Standard 33

Página 29

Figure 18 - Typical water to water integration points list 35

Página 30 - Control Mode

BACview Termination Detail 36

Página 31

RS-Sensor Termination Detail The RS Sensor is remotely mounted and installed (up to 500ft) in the zone it is recommended to use shielded cable (20AW

Página 32

38 The RS-Pro Sensor interface The RS-Pro sensor factory part number 641-230 is a combination keypad/display unit that attaches to a con

Página 33

IMPORTANT: By Pressing the Info button on the sensor the user can see the following typical data: INFO PRESS 1 – Displays occupancy override ti

Página 34

The Zone Controller The Zone control board also known as DDC and shown in figure 1 is used in most configure to order applications. It is BA

Página 35

40 NOTES

Página 37 - RS-Sensor Termination Detail

42 601 N.W. 65th Court, Ft. Lauderdale, FL 33309 Phone: 954-776-5471 Fax: 954-776-5529 www.fhp-mfg.com 970-443

Página 38 - The RS-Pro Sensor interface

Specifications Power: 24VAC ± 10%, 50-60Hz, 20VA power consumption (Single Class II 70VA or 100VA option available) Physical: R

Página 39

6 Controller Components Controller Components LED Indicators LED Indicators The DDC controller is equipped with three bank sets of LED tha

Página 40

Figure 4 – Digital Output LEDs The Third Bank of LEDs are located on the bottom right corner of the controller as shown on figure 4 (ri

Página 41

8 PROTOCOLS SW3 SW4 BACnet® MS/TP Off Off N2 On Off Modbus Off On Option Card On On Typical DIP switch for LonTalk® (Option Card) is shown

Página 42

LonWorks® card option LonWorks® is a network platform that allows any facility or to integrate sub-systems using a common system archi