Bosch D9412GV2 Guia de Instalação Página 83

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 158
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 82
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 83
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Summary Trouble
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Non-fire point in the control panel
is in a trouble condition. This relay provides a steady
output until the user at the keypad acknowledges the
trouble.
Summary SupBurg
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Non-fire Supervisory point in the
control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay provides
a steady output until the user at the keypad
acknowledges the condition.
Vista de página 82
1 2 ... 78 79 80 81 82 83 84 85 86 87 88 ... 157 158

Comentários a estes Manuais

Sem comentários