GoTo/CA-EDC 04.13 E Electric Drives and Controls GoTo Canada Bosch Rexroth Canada 25
2, 4, 8 channel modules available. Can read full range of standard
thermocouples and resistive inputs. Spring-cage I/O connectors utilized
for easy wiring.
Inline – Temperature Modules
GoTo Focused Delivery Program: I/O
Features
• Pt, Ni, Cu, KTY, linear resistors can be used with RTD modules
• B, C, E, J, K, L, N, R, S, T, U, W, thermocouples can be used with UTH
• 2-, 3-wire inputs available depending on your needs
Technical Data
R-IB IL TEMP 2 RTD-PAC
Analog inputs
Number 2 inputs for resistive temperature sensors
Usable sensor types Pt, Ni, Cu, KTY
Conversion time of A/D converter Typ. 120 µs
Voltage input range –
Process data update Depending on connection method
Both channels acc. to two-wire principle 20 ms
One channel acc. to two-wire principle,
one channel acc. to four-wire principle
20 ms
Both channels acc. to three-wire principle 32 ms
Limit frequency of analog filter –
Sensor connection type 2-, 3- or 4-wire connection
Electric data
Logic voltage U
L
7.5 V
Power consumption from local bus U
L
Typ. 43 mA
Peripheral supply voltage U
ANA
24 V DC
Power consumption at U
ANA
Typ. 11 mA
Error message to the higher level
control system
Failure of supply voltage U
ANA
, peripheral/user error
Mechanical data
Dimensions (W x H x D) 12.2 x 135 x 71.5 mm
Protection category IP20
Protection class Class 3 according to VDE 0106, IEC 60536
Accessories Connectors and labels included