ISW-D8125CW-V2 | Installation and Operation Guide | Troubleshooting
18 Bosch Security Systems, Inc. | 8/11 | F01U161691-05
Symptom Diagnosis Remedy
in RF Diagnostics
Received signal level for that point is low. A second EN4200 receiver can be
installed in a different location to
increase range. A Bosch EN5040-T
high-power repeater may be used to
increase range to a greater degree.
Use the EN7016 to test the signal
range.
in RF Diagnostics
Commercial wireless interface module has
not received enough recent transmissions
from that RF point to give an 'OK' or 'BAD'
signal indication; Several transmissions are
required. The signal indication will start out
as '?' after power up, after programming an
RF point, or after an RF point has gone
missing.
Cause several transmissions to
update signal level. About 4 alarms
or tampers and 4 restorals spaced 5
seconds apart will cause enough
transmissions to get an accurate
signal indication. Without
activations, it will take approximately
90 minutes to get an adequate
number of signal strength readings.
RF points go missing when
programmed supervision interval =
none.
These RF Points are programmed as Fire
Points. Transmitters programmed as Fire
points will be supervised at 4 hour intervals,
regardless of programmed supervision
interval time.
If those RF points are not for Fire
devices, reprogram the transmitter as
new, changing the transmitter point
type to Burg.